EPICHLOROHYDRIN
1010
CH2OCHCH2Cl
MW: 92.53
CAS: 106-89-8
METHOD: 1010, Issue 2
EVALUATION: FULL
Issue 1: 15 February 1990
Issue 2: 15 August 1994
OSHA:
5 ppm (skin)
NIOSH:
lowest feasible (carcinogen)
ACGIH:
2 ppm (skin) (carcinogen)
(1 ppm = 3.78 mg/m3 @ NTP
(1 ppm = 3.78 mg/m3 @ NTP
PROPERTIES:
liquid; d 1.1812 g/mL @ 20 °C;
BP 117.9 °C; MP 25.6 °C;
VP 1.67 kPa (12.5 mm Hg;
16,400 ppm) @ 20 °C; explosive range
BP 117.9 °C; MP 25.6 °C;
VP 1.67 kPa (12.5 mm Hg;
16,400 ppm) @ 20 °C; explosive range
SYNONYMS: chloropropylene oxide; 1-chloro-2,3-epoxypropane; chloromethyloxirane
SAMPLING
SAMPLER:
SOLID SORBENT TUBE
(coconut shell charcoal, 100 mg/50 mg)
(coconut shell charcoal, 100 mg/50 mg)
FLOW RATE:
0.01 to 0.2 L/min
VOL-MIN:
2 L @ 5 ppm
-MAX:
30 L
SHIPMENT:
routine
SAMPLE STABILITY:
at least 2 weeks @ 25 C [1]
BLANKS:
2 to 10 field blanks per set
ACCURACY
RANGE STUDIED:
12 to 43 mg/m3 [2]
(20-L samples)
(20-L samples)
BIAS:
4.2%
OVERALL PRECISION (SrT):
0.057 [2]
ACCURACY:
± 14.3%
MEASUREMENT
TECHNIQUE:
GAS CHROMATOGRAPHY, FID
ANALYTE:
epichlorohydrin
DESORPTION:
1 mL CS2; stand 30 min
INJECTION VOLUME:
5 µL
TEMPERATURE-INJECTION:
175 °C
-DETECTOR:
215 °C
-COLUMN:
135 °C
CARRIER GAS:
N2 or He, 20 mL/min
COLUMN:
1.8 m x 2-mm ID glass; 80/100 Chromosorb 101 [1]
CALIBRATION:
epichlorohydrin in CS2
RANGE:
0.04 to 1.2 mg per sample [2]
ESTIMATED LOD:
1.0 µg per sample
PRECISION (Sr):
0.031 [2]
APPLICABILITY: The working range is 0.5 to 16 ppm (2 to 60 mg/m3) for a 20-L air sample.
INTERFERENCES: None identified.
OTHER METHODS: This is Method S118 in a revised format [3]. A similar method appears in the criteria document [4].
NIOSH Manual of Analytical Methods (NMAM), Fourth Edition